Metal Oxide Varistors (MOV)

While an Metal Oxide Varistors (MOV) is designed to conduct significant power for very short durations (about 8 to 20 microseconds), such as caused by lightning strikes, it typically does not have the capacity to conduct sustained energy. Under normal utility voltage conditions, this is not a problem. However, certain types of faults on the utility power grid can result in sustained over-voltage conditions. Examples include a loss of a neutral conductor or shorted lines on the high voltage system. Application of sustained over-voltage to a mov metal oxide varistor can cause high dissipation, potentially resulting in the MOV device catching fire. The National Fire Protection Association (NFPA) has documented many cases of catastrophic fires that have been caused by MOV devices in surge suppressors, and has issued bulletins on the issue.

A 130 volt, 150 J MOV that has undergone catastrophic failure, apparently as a result of a lightning strike, showing evidence of heat and smoke. The 3 amp fast-blow fuse immediately in front of the varistor blew during the same event.
A series connected thermal fuse is one solution to catastrophic MOV failure. Varistors with internal thermal protection are also available.
There are several issues to be noted regarding behavior of transient voltage surge suppressors (TVSS) incorporating MOVs under over-voltage conditions. Depending on the level of conducted current, dissipated heat may be insufficient to cause failure, but may degrade the MOV device and reduce its life expectancy. If excessive current is conducted by a MOV, it may fail catastrophically, keeping the load connected, but now without any surge protection. A user may have no indication when the surge suppressor has failed. Under the right conditions of over-voltage and line impedance, it may be possible to cause the MOV to burst into flames,[5] the root cause of many fires[6] and the main reason for NFPA’s concern resulting in UL1449 in 1986 and subsequent revisions in 1998 and 2009. Properly designed TVSS devices must not fail catastrophically, resulting in the opening of a thermal fuse or something equivalent that only disconnects MOV devices.

2015年11月9日星期一

the Specifications of metal oxide varistor application

Voltage rating
MOVs are specified according to the voltage range that they can tolerate without damage. Other important parameters are the metal oxide varistor application energy rating in joules, operating voltage, response time, maximum current, and breakdown (clamping) voltage. Energy rating is often defined using standardized transients such as 8/20 microseconds or 10/1000 microseconds, where 8 microseconds is the transient's front time and 20 microseconds is the time to half value.
Response time
The response time of the varistors is not standardized. The sub-nanosecond MOV response claim is based on the material's intrinsic response time, but will be slowed down by other factors such as the inductance of component leads and the mounting method. That response time is also qualified as insignificant when compared to a transient having an 8 μs rise-time, thereby allowing ample time for the device to slowly turn-on. When subjected to a very fast, <1 ns rise-time transient, response times for the MOV are in the 40–60 ns range.
Capacitance

Typical capacitance for consumer-sized (7–20 mm diameter) varistors are in the range of 100–1,000 pF. Smaller, lower-capacitance varistors are available with capacitance of ~1 pF for microelectronic protection, such as in cellular phones. These low-capacitance varistors are, however, unable to withstand large surge currents simply due to their compact PCB-mount size.

2015年11月4日星期三

the introduction of metal oxide varistors application

Traditional Metal oxide varistors schematic symbol. It expresses the diode-like behavior in both directions of current flow.
Modern varistor schematic symbol.
metal oxide varistors application is an electronic component with an electrical resistance that varies with the applied voltage. Also known as a voltage-dependent resistor (VDR), it has a nonlinear, non-ohmic current–voltage characteristic that is similar to that of a diode. In contrast to a diode however, it has the same characteristic for both directions of traversing current. At low voltage it has a high electrical resistance which decreases as the voltage is raised.

Varistors are used as control or compensation elements in circuits either to provide optimal operating conditions or to protect against excessive transient voltages. When used as protection devices, they shunt the current created by the excessive voltage away from sensitive components when triggered.
The development of the varistor, in the form of a new type of rectifier (copper oxide), originated in the work by L.O. Grondahl and P.H. Geiger in 1927. The name varistor is a portmanteau of varying resistor. The term is only used for non-ohmic varying resistors. Variable resistors, such as the potentiometer and the rheostat, have ohmic characteristics.